Altech On-load Changeover Switch find a wide application scope where the reliability of electrical supply from the utility is low and are used in lighting/motor circuits where continuity of supply is necessary, for switching to an alternative source from main supply and vice versa.
They are switch disconnectors with independent manual operation capable of making, carrying and breaking currents under normal circuit conditions such as short circuit for a specified time,
These switches are modular in construction compact in size and suitable for stringent utilization category AC-23A/B.
Onload change over switch Technical Data |
S. No. | Specification (IS / IEC 60947- 3) | Unit | Frame Size 00 | Frame Size 1 | Frame Size 2 | Frame Size 3 | |||||
1 | Rated operational current, I | A | 63 | 100 | 125 | 160 | 200 | 250 | 320 | 400 | 630 |
2 | Conventional free air thermal current, Ith | A | 63 | 100 | 125 | 160 | 200 | 250 | 320 | 400 | 630 |
3 | Rated uninterupted current, Iu | A | 63 | 100 | 125 | 160 | 200 | 250 | 320 | 400 | 60 |
4 | No. of Poles | 4 | 4 | 4 | 4 | 4 | 4 | 4 | 4 | 4 | |
5 | Rated insulation voltage, U | Vac | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 |
6 | Rated operational voltage, Ue | Vac | 415V | 415V | 415V | 415V | 415V | 415V | 415V | 415V | 415V |
7 | Di-electric strength, 50 Hz | kV | 5 | 5 | 5 | 5 | 5 | 5 | 5 | 5 | 5 |
8 | Rated impulse withstand voltage, Uimp | kV | 8 | 8 | 8 | 8 | 8 | 8 | 8 | 8 | 8 |
9 | Utilization Category | AC23 A | |||||||||
10 | Conventional Enclosed Thermal Current at 40 °C, Ithe | A | 63 | 100 | 125 | 160 | 200 | 250 | 320 | 400 | 630 |
11 | Rated making capacity Amp, 436 Vac 23 A, p.f.- 0.35 | A | 630 | 100 | 1250 | 1600 | 2000 | 2500 | 3200 | 4000 | 6300 |
12 | Rated breaking capacity Amp, 436 Vac 23 A, p.f.- 0.35 | A | 504 | 800 | 1000 | 1280 | 1600 | 2000 | 2560 | 3200 | 5040 |
13 | Rated operational power at 415 V, 3ø | kW | 36 | 58 | 72 | 92 | 115 | 144 | 184 | 230 | 362 |
14 | Rated conditional short circuit current | kA rms | 80 | 80 | 80 | 80 | 80 | 80 | 80 | 80 | 80 |
15 | Max. Allowed cut off current | kA peak | 17 | 18 | 22 | 27 | 33 | 39 | 55 | ||
16 | No. of operating cycles AC – 23 A | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | |
17 | No. of no load operating cycles | 10000 | 10000 | 10000 | 10000 | 10000 | 10000 | 8000 | 8000 | 8000 | |
18 | Temperature withstand range (Ambient) | °C | ,-5 to 50 | ,-5 to 50 | ,-5 to 50 | ,-5 to 50 | ,-5 to 50 | ,-5 to 50 | ,-5 to 50 | ,-5 to 50 | ,-5 to 50 |