| Standard |
IEC 60364-4-43. |
| Rated insulation Voltage Ul |
690V |
| Rated impulse withstand voltage Uimp |
8kV |
| Rated working voltage Ue |
AC220V/AC110V |
| Rated Frequency |
50/60Hz |
| Class |
PC Class: can be switched on and loaded without generating short- circuit current |
| Pole number |
DP |
| Rated short-circuit current lq |
5kA |
| Short circuit protection device (fuse) |
63A |
| Rated impulse withstand voltage |
8kV |
| Control circuit |
Rated control voltage us: AC220V |
| Auxiliary circuit |
AC220V/110V 50Hz le=5A |
| Contactor change -over time |
<50ms |
| Operation Change-over time |
<50ms |
| Returne Change-over time |
<50ms |
| Power off time |
<50ms |
| Change-over operation time |
<50ms |
| Mechanical life |
>8000 times |
| Electrical life |
>1500 times |
| Usage category |
AC-31B |
| Working Temperature |
-5 to 40 C |