Phone: +91 70609 99496

MCB FP


        	

MCB FP

MCB has the characteristics of advanced structure, reliable performance, high breaking capacity and beautiful appearance. It is mainly used for AC 50HZ or 60HZ, rated voltage 240/415V or below and rated working current 63A or below. It is used for overload and short-circuit protection of lighting, distribution lines, equipment in office buildings, residential buildings and etc. It can also be used for infrequent on-off operations and conversion of lines.

                         MCB  techinical data
S.NO Technical Information MCB
1 Standard conformity IS/IEC60898-1:2015
2 Rated current (In)                     (A) 0.5 - 63*
3 Rated Voltage (Ue)                         V~ 240/415
4 No of pole (Execution) 1P,1P+N,2P,3P,3P+N,4P
5 Rated Frequency                           (Hz) 50/60
6 Rated short-circuit Breaking capacity (kA) 6 & 10
7 Type/Series B C
8 Magnetic Release Setting (3-5)In (5-10)In
9 Rated Insulation Voltage (Ui)    V  660 V
10 Rated Impulse Voltage (Uimp)(KV) 4
11 Energy Limiting Class               (ELC) 3
12 Protection Class IP20
13 Electrical/Mechanical Endurance Test (No of Operation)
<32A 20000
>32A 10000
14 Vibration (g) 3
15 Shock test 40mm free fall
16 Reference Ambient Temp           (°C) 30
17 Terminal Capacity                     (mm²) 25
18 Ambient Working Temperature -5°C to 55°C
19 Storage Temperature -25°C to +70°C
20 Mounting Din Rail Clip
21 Installation Position Vertical/Horizontal
22 Case & Cover Moulded, flame-retardant thermoplastics material